TABLE 2: BRICK AND MORTAR SPECIFICATIONS |
This table offers the appropriate specification of clay bricks and mortar for various building types |
Situation | Brick durability | Ìý | Mortar designation | Remarks |
Ìý | BS 3921 | EN 771-1 | Ìý | Ìý |
Work below or near external ground level |
Low risk of saturation, with or without freezing | FL, FN, ML or MN | F1 or F2: S1 or S2 | (i), (ii) or (iii) | Ìý |
High risk of saturation, with freezing | FL FN F2: | F2: S2 S1 | (i) or (ii) (i) or (ii*) | * with SRPC |
Drainage manholes | FL, FN, ML or MN | F1 or F2:S1 or S2 | (i) | Ìý |
External walls of buildings (unrendered) excluding chimneys, parapets, cappings, copings and sills |
Low risk of saturation | FL, FN, ML or MN | F1 or F2:S1 or S2 | (i), (ii) or (iii) | Ìý |
High risk of saturation | FL FN | F2: S2 F2: S1 | (i) or (ii) (i) or (ii*) | * with SRPC |
Parapet walls (unrendered) |
Low risk of saturation, e.g. low parapets with copings on some single storey buildings | FL or ML FN or MN | F1, F2: S2 F1, F2: S1 | (i), (ii) or (iii) (i), (ii*) or (iii*) | * with SRPC |
High risk of saturation, e.g. where only a capping is provided | FL FN | F2: S2 F2: S1 | (i) or (ii) (i) or (ii*) | * with SRPC |
Cappings, copings and sills |
Cappings, copings and sills | FL or FN | F2: S1 or S2 | (i) | Bed DPCs under cappings, copings and sills in the same mortar |
Freestanding garden walls |
With coping | FL or ML FN or MN | F1, F2: S2 F1, F2: S1 | (i), (ii) or (iii) (i) or (ii) | (ii) mortar with SRPC in exposed locations |
With capping | FL FN | F2: S2 F2: S1 | (i) or (ii) (i) or (ii) with SRPC | Ìý |
Earth retaining walls * Backfilling with free-draining material is strongly recommended |
With coping and waterproof membrane on retaining face | FL or ML FN or MN | F1, F2: S2 F1, F2: S1 | (i) or (ii) (i) or (ii*) | * with SRPC |
With capping, or with coping but no waterproof membrane on retaining face | FL or FN | F2: S1 or S2 | (i) | A waterproof membrane on the retaining face is strongly recommended |
Note: BS 3921: 1985, the British Standard Specification for Clay Bricks, is in the process of being replaced by BS EN 771-1: 2003, the European Standard for Clay Masonry Units. They will run concurrently until early 2005. |
Key |
Designation letters for brick durability and soluble salts content differ between BS 3921 and EN 771-1. |
In BS 3921:1985 |
Brick durability: F=frost resistant M=moderately frost resistant O=not frost resistant |
Soluble salts content: L=low soluble salts content N=normal soluble salts content |
In BS EN 771-1:2003 |
Brick durability: F2=severe exposure F1=moderate exposure F0=passive exposure |
Soluble salts content: S2=lower content category S1=higher content category S0=No requirement category |
SRPC=Sulphate resisting Portland cement |